CTLJT ­ Test 2002.
Test report for 2" SDR. 11 standard coupling, male thread.
The test was performed during 08/19/02 and 09/30/02.
Total hours 1006.
 
The test was conducted according to requirements in ASTM F 1588 ­ 96.
 
The coupling was tested without an insert and is classified as a mechanical joint
Category 1 ­ in ASTM D 2513.
The load was calculated as specified in ASTM F 1588, under load calculation method 1:
Internal test pressure varied between 80 and 130 PSI.
Dead load weight was 1450 Lbs.
Max internal pressure was calculated at 100 PSI.
Total weight 1450 + 445 = 1895 Lbs.
 
Hoop stress in crossectional area was calculated to 1290 PSI.
 
At the end of the test a total elongation of the sample was measured to 0.137"
No slippage were detected between pipe and coupling, and no pullout had occurred.
 
The test were performed at 75 Deg. F + 5 Deg,
 
The sample was checked for leakage on a daily schedule.
No leakage was detected at any time.
 

This test was performed successfully and the results satisfied the
requirements of ASTM F 1588.

 
Q.A. Manager
POLY-CAM Inc.

POLY-CAM pressure testing facility